The most fire multifunctional temperature inspecti

2022-09-26
  • Detail

Application of multifunctional temperature inspection and control device in the fire protection system of boiler room in power plant

abstract the problems existing in the fire protection system of Mitsubishi unit boiler room are analyzed, and the improvement measures are put forward. By applying the multi-functional temperature inspection and control device to the steam heat tracing system of fire pipeline, the problem of automatic control of water temperature in fire pipeline in winter is solved

keywords fire protection system steam tracing temperature control

0 introduction

Hejin Power Plant Phase I project 2 × 350 MW units are imported from Mitsubishi Corporation of Japan The boiler room is arranged in the open air, with a height of 63 5 m。 The fire-fighting system of boiler room adopts pressurized water fire-fighting system, and the normal pressure of the system is maintained at 0,8 MPa. A fire water ring header is designed at the bottom of the boiler room, and a dn 150 fire water supply pipe from bottom to top is designed at the four corners of the boiler room. According to the height of the maintenance platform of the boiler room, connect the universal testing machine on each floor of the maintenance platform. If there is an accident, immediately terminate the experiment with 7 fire hydrants of DN 65. According to the climatic characteristics of the local average temperature of - 10 ~ - 20 ℃ in winter, Mitsubishi company designed a double circuit steam tracing system on the fire pipe of the boiler room, and used rock wool and aluminum sheet for insulation outside the fire pipe. The heat tracing steam of the fire pipe is taken from the low-temperature auxiliary steam header of the unit, and the steam parameter is p= 0, 6 MPa, t=150 ℃. Since the 1 #, 2 # units were put into operation successively in 2000, due to the deficiencies in the design of the fire protection system of the boiler room, frequent leakage faults occurred in the pipeline of the fire protection system, which seriously affected the normal operation of the system. By analyzing and studying the problems existing in the original fire protection system, the author puts forward corresponding improvement measures. Among them, the self-developed multi-channel temperature inspection and control device has successfully solved the problem of automatic control of steam tracing temperature of fire pipe in boiler room, and achieved good operation results

1 problems existing in the original fire-fighting system

the boiler room fire-fighting system designed by Mitsubishi company mainly has the following problems: ① the number of isolation valves on the fire-fighting system pipeline of the boiler room is small, resulting in the need for large-scale isolation and drainage work in case of maintenance work of the fire-fighting system, which not only prolongs the maintenance time, but also is detrimental to fire safety; ② According to the requirements of China's fire protection design code, the fire pipes in the boiler room are connected by flanges, and the rubber seal ring connected by flanges is easy to age and fail, causing the leakage fault caused by flange connection; ③ There are no U-shaped expansion bends and elastic supports and hangers designed on the pipes of the fire protection system, which makes the pipes unable to expand freely when the heat tracing system of the fire protection pipeline is put into operation in winter, and has caused the cracking and leakage of the weld joint of the pipe elbow for many times; ④ The heat tracing steam of the fire pipeline is manually controlled. Because the temperature of the heat tracing steam is too high, the water temperature in the fire pipeline cannot be monitored, which brings great difficulties to the operation of operators. If the steam tracing system operates for a long time, the water temperature in the fire pipe will be heated to 80~90 ℃; If the exit time is too long, the fire pipeline will have frost crack leakage fault. Due to the above problems, the fire protection system of the boiler room has been unable to operate normally in winter, which has seriously affected the fire safety work and increased the overhaul and maintenance workload of the overhaul personnel

2 technical transformation measures

in view of the problems existing in the fire-fighting system of the boiler room, the following technical transformation measures are mainly adopted: ① isolation valves are installed on the fire-fighting water supply main pipe of the 1 #, 2 # boiler room and the fire-fighting water supply riser at the four corners of the boiler room respectively, so that the fire-fighting system of the 1 #, 2 # boiler becomes a unit system design, reducing the system isolation operation and drainage time in the maintenance work; ② Replace the rubber gasket between the flanges of fire pipes with steel wire wound gasket to improve the tightness and reliability of flange joint; ③ Four U-shaped expansion bends are installed on the fire water supply main pipe of 1 #, 2 # boiler room respectively, and two U-shaped expansion bends are installed on each fire water supply riser of the boiler room to absorb the stress changes caused by the thermal expansion and cold contraction of the fire pipe; ④ A set of multifunctional temperature inspection and control device suitable for the steam tracing temperature control of several fire-fighting pipelines has been developed by ourselves, which realizes the automatic detection and control function of the water temperature in the fire-fighting pipelines, so that the water temperature of the fire-fighting system in the boiler room is maintained between 10~40 ℃ during winter operation. This technical transformation measure provides successful experience for solving the problem that the fire protection system of boiler room in power plants in northern China can not operate normally. The following focuses on the working principle and application effect of the multi-channel temperature inspection and control device

3 multi channel temperature inspection and control device

3 1 working principle

according to the operation requirements of the fire protection system in the boiler room of the power plant, the normal operation of the whole fire protection system can be guaranteed as long as the water temperature in the fire protection pipeline is not lower than 5 ℃ in winter. As the boiler room of the power plant is generally arranged outdoors, the water temperature in the fire pipeline is greatly affected by different wind directions in winter, so it is impossible to keep the water temperature of the whole fire protection system constant, and the temperature can only be controlled within a reasonable range. According to the above characteristics, two thermocouple measuring points and two local thermometers are installed on each fire water supply riser at the four corners of the boiler room to monitor the water temperature changes in each fire pipe. The thermocouple and the local thermometer are respectively installed at 12 5 m and 47 m positions are convenient for patrol inspection and maintenance. An electric shut-off valve is installed behind the manual shut-off valve of the heat tracing steam of the fire pipe in the boiler room to automatically open and cut off the heat tracing steam of the fire pipe. A dn 50 fire water ring connecting pipe is installed on the 47m platform of the boiler room, and the principles of heat balance and microcirculation are applied to reduce the temperature difference of each fire water supply riser due to different installation positions and the influence of wind direction. A set of multifunctional automatic temperature inspection and control device is installed on the 12.5m maintenance platform of 1# boiler room to automatically inspect and control the water temperature in the fire pipe of the boiler room. According to the actual use effect of the multifunctional automatic temperature inspection and control device in Hejin Power Plant, in order to reduce the influence of wire resistance on the measurement signal in the process of temperature signal transmission, the maximum service radius of the wooden device should not exceed 500m. When the temperature of a measuring point reaches 5 ℃, the multi-functional automatic temperature inspection and control device sends out a control command, automatically opens the electric shutoff valve of the heat tracing steam of the fire pipeline, and the steam tracing system of the fire pipeline is put into operation to start to improve the water temperature in the fire pipeline; When the temperature of a measuring point reaches 45 ℃, the multi-functional automatic temperature inspection and control device sends out a control command, closes the electric shut-off valve of the heat tracing steam of the fire pipeline, the steam heat tracing system of the fire pipeline stops running, and the fire water in the fire pipeline enters the stage of insulation and heat microcirculation. When the temperature of a measuring point is lower than 5 ℃ or higher than 45 ℃, the multifunctional automatic temperature inspection and control device will send an alarm signal to remind the operator to take corresponding treatment measures. Figure 1 shows the working principle of the multifunctional automatic temperature inspection and control device

3.2 operation effect

the operation practice in the past two years shows that the device operates stably, the detection and control functions are reliable, the operation of operators is greatly reduced, and good actual operation effect is achieved. According to the operation records of the fire-fighting system in the boiler room, the steam heat tracing system of the fire-fighting pipeline is put into operation for an average of 2-4 times per person in winter, and each time it is put into operation for 2.5-3.5 hours. The water temperature in the fire-fighting pipeline of the whole boiler room is generally maintained between 5-45 ℃, and there is no pipeline frost crack or thermal expansion leakage fault, which significantly reduces the overhaul and maintenance workload of the fire-fighting system in the boiler room

3 3 problems encountered in commissioning and suggestions for improvement

since this transformation has not made too big changes to the original fire protection system, we encountered the following main problems when commissioning the multi-function automatic temperature inspection and control device

(1) due to the different positions of each fire water supply riser at the four corners of the boiler room, when encountering windy weather in winter, the water temperature in the windward side pipe is very different from that in the leeward side pipe. According to the on-site commissioning records, the maximum temperature difference has exceeded 40 ℃, resulting in the failure of the multi-functional automatic temperature inspection and control device to adjust and control the temperature normally, and constantly sending the opening and closing commands of the electric shut-off valve of heat tracing steam alternately. Through the careful analysis of the heat tracing system of the fire pipeline, it is found that the causes of the above problems are not only the influence caused by the different installation positions of the fire pipeline, but also the different direction and diameter of the heat tracing steam are the main reasons for the excessive water temperature deviation. It is necessary to further transform the heat tracing system to completely solve the problem of excessive temperature difference. In order to ensure the normal operation of the multi-function automatic temperature inspection and control device before the transformation of the fire pipe heat tracing system, the operators need to manually adjust the opening of the heat tracing steam isolation valve in a certain area under this working condition, and reduce the water temperature deviation in the fire pipe to improve the circulation efficiency to 30~35 ℃ by controlling the heat tracing steam flow in different areas

(2) considering the convenient monitoring of operators, the wood transformation will install two multi-functional automatic temperature inspection and control devices in 1# and 2# boiler rooms on 12 of 1# boiler 5 m maintenance platform. Due to the long distance from the control panel to the 2# boiler room, the wire resistance of the temperature transmission circuit exceeds 5, resulting in excessive temperature measurement error. According to theoretical calculation, the resistance value of copper conductor per kilometer of lmm2 is about 1 7. There are two temperature points in the 2# boiler room in the wood transformation. The distance from the multifunctional automatic temperature inspection and control device is about 400 m Its resistance value is about 6 8 . This value exceeds the allowable range of normal operation of metal platinum resistance thermocouple 5. The above measuring points are treated by bridge resistance balance technology The temperature measurement error is basically eliminated. The specific balance method is shown in Figure 2. According to the resistance balance principle of temperature measurement circuit: R 14= R 24= R 35= R C + r u =5 ± 0 01 。

(3) the shielding effect in the temperature signal transmission circuit directly affects the stability of the temperature measurement system. Since cables for various purposes are simultaneously laid near the temperature signal transmission cables of the fire pipelines in the 1 #, 2 # boiler room, poor circuit shielding will cause instability of the temperature measurement signal. During the commissioning, the temperature change with unknown reasons was encountered many times. After full technical analysis and system measurement, it was finally found that the cause of the problem was the poor shielding grounding of some temperature signal transmission circuits. After improving the shielding grounding mode, the temperature signal automatically returned to normal

4 conclusion "The surface area of carbon nanotubes reaches 1000 times that of carbon fibers

at present, the boiler rooms of units above 300 MW in China mostly adopt the outdoor exposed layout. In the northern region, due to climate reasons, the fire pipes in the boiler room need to be designed with not only rock wool and aluminum skin to keep the temperature, but also need to be equipped with a steam tracing system. Because the temperature of the steam tracing system is inconvenient to monitor and control, and the operation of operators is difficult, many reasons exist In winter, the power plant had to take measures to isolate the fire-fighting system of the boiler room, leaving hidden dangers for the fire-fighting safety of the boiler room. The technical transformation experience of the fire protection system in the boiler room of Hejin Power Plant will undoubtedly provide a useful reference for the design of the fire protection system of new units and the technical transformation of operating units

Copyright © 2011 JIN SHI